150 PSI Single Corrosion Liner (SCL)


 

Pipe DIAMETER Inches
I.D. Inches
O.D. Inches
Wall Thickness Inches
LBS/FT
Max Hanger Spacing Feet
1 1 1.38 0.19  0.55 
2 2 2.38 0.19 0.80 6
3 3 3.5 0.25 2.02 8
4 4 4.5 0.25 2.64 8.5
5 5 5.63 0.31 4.13 10.5
6 6 6.43 0.22 3.35 10.4
8 8 8.51 0.25 4.85 11.5
10 10 10.58 0.29 7.90 13
12 12 12.66 0.33 9.73 14
14 14 14.73 0.37 14.2 15.5
16 16 16.81 0.40 15.8 17
18 18 18.82 0.44 18.55 17.5
20 20 20.96 0.48 20.65 18.5
24 24 25.11 0.55 29.95 20
30 30 31.33 0.67 49.45 22.5

 

Notes:
Sizes 1" through 5" are hand-lay-up, Sizes 6" and above are filament wound.
Safety factor 10:1, 150 psi rating discounting liner.

Fiberglass Reinforced Plastic Systems

150 PSI Double Corrosion Liner (DCL)


 

Pipe DIAMETER Inches
I.D. Inches
O.D. Inches
Wall Thickness Inches
LBS/FT
Max Hanger Spacing Feet
1 1 1.58 0.29  0.92
2 2 2.58 0.29 1.64 6
3 3 3.7 0.35 2.91 8
4 4 4.7 0.35 3.78 8.5
5 5 5.83 0.41 5.56 10.5
6 6 6.63 0.32 4.97 10.4
8 8 8.71 0.35 7.36 11.5
10 10 10.78 0.39 10.11 13
12 12 12.86 0.43 13.27 14
14 14 14.93 0.47 19.77 15.5
16 16 17.01 0.50 20.70 17
18 18 19.02 0.54 24.96 17.5
20 20 21.16 0.58 29.65 18.5
24 24 25.31 0.65 40.13 20
30 30 31.53 0.77 59.65 22.5

Notes:
Sizes 1" through 5" are hand-lay-up, Sizes 6" and above are filament wound.
Safety factor 10:1, 150 psi rating discounting liner.


FRP Systems
804 Macdonell St. Thunder Bay, Ontario P7B 4A6 - (p) 807.345.2171 - (F) 807.345.8215 - (E) info@frpsystems.com